- Pressure range: 0.0 to 4.6 MPa g (g: gauge)
- Working temperature:-30°C to 135°C
- Power supply voltage (Vin): 5.0 +/- 0.1 VDC
- Output voltage (Vout): 0.89 to 4.5 V typical
- Initial accuracy:+/- 2.5% Vdd at -30°C to 135°C. Vdd = DC5.0V
- Overall accuracy:+/-3.5% Vdd at -30°C to 135°C. Vdd = DC5.0V。
- Power supply current: 10 mA Max without load
- Pressure resistance: 1.5 times maximum working pressure
- Burst pressure: 2.0 times maximum working pressure
- Installation torque: 12.7 Nm +/-10%
- Drop test: 1.0 m on the concrete floor, no deformation once
- Overvoltage: DC 16V, 30sec
- Reverse voltage: DC -12V, 30sec
- Electrical connection: 10k ohm pull-down resistor
- Pressure connection: 1/4” SAE flammable thread socket: 7/16-20UNF 2B
- Pressure cycle life test: can withstand 5 million full working pressure cycles at room temperature
SST-Refrigeration and Air-conditioning and Industrial Control Pressure Switches and Sensors
- Model: 45CP
- Application: Inverter system control.
- This specification covers the use of solid-state pressure sensors in refrigerant air-conditioning systems for R22, R134a and R407C
- Sensata- Part:45CP2-1、45CP2-2、45CP2-3、45CP2-4、45CP2-5、45CP2-6、45CP2-7
- Withstand voltage: AC1500V 1sec (between each terminal and the body)